DENYO DCA-25ESI

Key Specs

  • Rated Output: 25 kVA
  • Fuel tank capacity: 70 L
  • Sound level: 64 dB

Key Features

  • High Performance
  • Dual Voltage System
  • Control Panel with Outstanding User-Friendliness
  • Provision of Various Protective Devices and Warning Lamps
  • Quiet Operation
 
 
 
 
 
 
 
 
Compare
Category: Tags: ,

Description

Frequency 60Hz
Rated Output Continuous kVA 25
Stand by kVA 27.5
No. of Phases     3-Phase, 4-Wire
Rated Voltage Dual Voltage V 190~240
V 380~480
Power Factor 0.8 (Lagging)
Voltage Regulation % Within ±0.5
Excitation Brushless, Rotating Exciter ( With A.V.R.)
Insulation Class F

Engine model Isuzu AA-4LE2
Type Inlined, Direct Injected
Number of cylinders-Bore×Stroke (mm) 4-85×96
Piston Displacement (L) 2.179
Rated output (PS/rpm) 32/1800
Rated output (kW/rpm) 3.5/1800
Fuel ASTM No. 2 Diesel Fuel or Equivalent
Fuel consumption 75% load (L/h) 4.2
Lube Oil Sump Capacity (L) 8.5
Coolant Capacity (L) 6.6
Battery x Quantity 80D26R×1
Fuel tank capacity (L) 70
Engine Emissions Stage II (Japanese)

Dimensions (LxWxH) (mm) 1540 x 680 x 900
Dry weight (Kg) 564
Sound level at 7 meters dB(A) 1500/1800 rpm 64

Standard Equipment:
  • Super Silent Technology
  • Control panel without complicated electronics! Simple Analogue Dials are easier to operate and create fewer faults than sets controlled by Electronics, especially in very hot and dusty environments
  • Compact design
  • A circuit breaker is provided to protect the generator from shorting of the load circuit or an overload
  • An emergency stop device is provided to automatically detect an engine malfunction and shut down the unit, as well as a warning lamp
  • Equipped with Earth Leakage Relay to prevent electric shock

Options:
  • Automatic start and stop device for ATS connection
  • Three-way valve for connecting an external tank
  • Automatic transfer switch
  • Dual Voltage system
  • Exhaust Pipe
  • Salt Corrosion Protection